Kromschroder FCU 500WC0F0H1K2-E, protective system control (88621239)
Brand: Kromschroder
SKU:
88621239
Kromschroder
88621239
Kromschroder protective system control
Housing for control cabinet installation, for monitoring and controlling central safety functions in multiple burner systems on industrial furnaces, long service life due to replaceable power module for fail-safe outputs. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft. EC-type tested and certified, CSA and FM approved, certified for systems up to SIL 3 (compliant with PL e).
Series 500
Mains voltage: 230 V AC, 50/60 Hz
No integrated tightness control or POC
No capacity control
With temperature monitoring
Spring force connection terminals
EU certified, CSA and FM approved, certified for systems up to SIL 3 (compliant with PL e)
Individual packaging
10 Emergency stop with fault lock-out
12 High gas pressure protection with fault lock-out
13 Low pressure cut-off with fault lock-out
15 Air deficiency cut-out with fault lock-out
19 Safety time during operation: 1 s
22 Type S double thermocouple Pt10Rh-Pt
23 Temperature difference limit value: 50°C
24 Lower limit for high temperature operation: 750°C
25 Upper limit of the furnace or flue gas temperature: 1350°C
26 Temperature hysteresis: 50°C
27 Pre-purge during high temperature operation
29 Fan switched on in the event of fault
30 Fan run-up time tGV: 0 s
31 Fault lock-out if fan not running
32 Air flow monitoring during controlled air flow on, valve opens
34 Pre-purge time tPV: 6000 s
35 Air flow monitoring during pre-purge with fault lock-out
37 Post-purge time tPN: 6000 s
38 Post-purge: actuator (if there is one) moves to the OPEN position and the air flow is not monitored.
62 Minimum pause time tfP: 0 s
63 Switch-on delay time tE: 0 s
65 Filling time before start-up: 0 s
67 Operating time in Manual mode limited to 5 min.
72 Function of terminal 67: fault lock-out if no signal from automatic burner control unit
77 User-defined password
80 Fieldbus communication: with address check
Housing for control cabinet installation, for monitoring and controlling central safety functions in multiple burner systems on industrial furnaces, long service life due to replaceable power module for fail-safe outputs. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft. EC-type tested and certified, CSA and FM approved, certified for systems up to SIL 3 (compliant with PL e).
Series 500
Mains voltage: 230 V AC, 50/60 Hz
No integrated tightness control or POC
No capacity control
With temperature monitoring
Spring force connection terminals
EU certified, CSA and FM approved, certified for systems up to SIL 3 (compliant with PL e)
Individual packaging
10 Emergency stop with fault lock-out
12 High gas pressure protection with fault lock-out
13 Low pressure cut-off with fault lock-out
15 Air deficiency cut-out with fault lock-out
19 Safety time during operation: 1 s
22 Type S double thermocouple Pt10Rh-Pt
23 Temperature difference limit value: 50°C
24 Lower limit for high temperature operation: 750°C
25 Upper limit of the furnace or flue gas temperature: 1350°C
26 Temperature hysteresis: 50°C
27 Pre-purge during high temperature operation
29 Fan switched on in the event of fault
30 Fan run-up time tGV: 0 s
31 Fault lock-out if fan not running
32 Air flow monitoring during controlled air flow on, valve opens
34 Pre-purge time tPV: 6000 s
35 Air flow monitoring during pre-purge with fault lock-out
37 Post-purge time tPN: 6000 s
38 Post-purge: actuator (if there is one) moves to the OPEN position and the air flow is not monitored.
62 Minimum pause time tfP: 0 s
63 Switch-on delay time tE: 0 s
65 Filling time before start-up: 0 s
67 Operating time in Manual mode limited to 5 min.
72 Function of terminal 67: fault lock-out if no signal from automatic burner control unit
77 User-defined password
80 Fieldbus communication: with address check
Replacing a Kromschroder FCU 500WC0F0H1K2-E, 88621239 protective system control is a good solution to make your equipment work again. We offer a wide range of Kromschroder spare parts for burners, gas trains etc. We supply original Elster (Kromschröder) & Honeywell (Maxon) products.
If you have any queries about Kromschroder control units or any other Kromschroder spare parts, please write us at 624burner@gmail.com, quoting the item code 88621239.
- Voltage 230 V AC
- Weight, kg 0,78
- Commodity code 90268020
- Country of origin DE