}, 1000) } });
0 Cart
Kromschroeder catalog
Honeywell catalog

Kromschroder BCU 580WC1F1U0D0K2-E, burner control unit (88670104)

Brand: Kromschroder
SKU: 88670104
Quantity:
+
PRICE ON REQUEST
624burner@gmail.com
Shipping methods

TNT delivery service

Pick up in our office

Payment methods

Invoice payment

Cash

Kromschroder burner control unit
Housing for control cabinet installation, for controlling, igniting and monitoring impulse-controlled, modulating or stage-controlled gas burners. For continuous operation with ionization control or UV control using Kromschroder UV sensor UVD. Intermittent operation with UV sensor UVS. Long service life due to replaceable power module for fail-safe outputs. Display of the program status, unit parameters and flame signal. Manual operating mode. Diagnosis and adjustment of unit parameters via optical interface using PC software BCSoft.
Version for pilot and main burners
EU certified, certified for systems up to SIL 3 (compliant with PL e)
Mains voltage: 230 V AC, 50/60 Hz
With valve proving system
Modulating capacity control with interface for actuator IC
Flammen?berwachung mit Ionisations- oder UV-Signal
Spring force connection terminals
Individual packaging
Flame control: ionization
01 Switch-off threshold, burner/pilot burner: 2 micro A
02 Main burner switch-off threshold: 2 micro A
07 Burner/pilot burner start-up attempts: 1
08 Burner start-up attempts: 1
09 Restart: burner
Safety time during operation: 2 s
40 Capacity control with IC 20
42 Running time: 250 s
44 Controller enable signal delay time tRF: 0 s
48 Controller enable following operating signal or in standby
49 Air actuator cannot be activated externally on start-up
50 Air actuator can be activated in the event of malfunction
51 Valve proving system: tightness test before start-up
52 Relief valve (VPS): V2
56 Measurement time Vp: 60 s
59 Valve opening time V1 (tL1): 3 s
61 Minimum burner on time tB: 0 s
62 Minimum pause time tBP: 0 s
67 Operating time in Manual mode limited to 5 min.
68 Function of terminal 50:purge with High signal
77 User-defined password
78 Burner application: burner and pilot burner
79 Pilot burner: continuous operation
94 1st safety time on start-up: 10 s
95 Flame proving period 1 tFS1: 0 s
96 2nd safety time on start-up: 3 s
97 Flame proving period 2 tFS2: 0 s
80 Fieldbus communication: with address check

Replacing a Kromschroder BCU 580WC1F1U0D0K2-E, 88670104 burner control unit is a good solution to make your equipment work again. We offer a wide range of Kromschroder spare parts for burners, gas trains etc. We supply original Elster (Kromschröder) & Honeywell (Maxon) products.

If you have any queries about Kromschroder burner control or any other Kromschroder spare parts, please write us at 624burner@gmail.com, quoting the item code 88670104.

  • Running time 250 s
  • Voltage 230 V AC
  • Weight, kg 0,85
  • Commodity code 90268020
  • Country of origin DE