Honeywell C7027A1023/U UV flame detector
Honeywell C7027A1023 UV sensors are used to detect the presence of ultra-violet radiation emitted by a flame. Flame detectors are used with Honeywell flame monitoring systems to detect the presence of flames in gas, oil and combined burners.
Features
• The C7027A1023/U flame detectors are used together with the R7249A, R7290A, R7749B and R7849A,B amplifiers and the corresponding Honeywell control devices.
• The Resideo C7027A1023/B flame sensor has a built-in cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.
• Due to its compact size, the Honeywell C7027A 1023 is well suited for installation on a purge pipe.
• When properly installed, the C7027A1023 can be used at pressures up to 5 psi.
• Two flame detectors C7027 A 1023 can be connected in parallel in cases where flame reading is difficult.
• The C7027A 1023/U photocell is only used with the R7851B flame amplifier and the corresponding Honeywell control devices.
• The flame detector C7027 A 1023/U has a built-in cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.
Specifications
• Ambient temperature: -18°C to 102°C or -40°C to +102°C, depending on the model.
• Maximum pressure: 5 psi (34.5 kPa).
• Installation: Cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.
• Electrical connections: Two wires 6 ft [1.83 m], color-coded, NEC Class 1. (One model comes with wires 24 ft [7.32 m] long). At the back of the detector there is a clamping contact for a ½-inch flexible metal conductor. (There are also models with a pressure contact and an internal thread of ½-inch).
• Spare Parts: Flange seal 129685
• Ambient temperature range: -18°C to +121°C or -40°C to +121°C, depending on the model.
• Maximum allowable pressure: 5 psi (34.5 kPa).
• Installation: Cuff with 1-11-1/2 NPSM internal thread for installation on a one-inch inspection tube. (DIN-certified model C7035A1064 has thread 1-11 BSP.P1).
Spare parts
1. Flange seal 129808
2. UV reading tube 139464M 18° – + 121°C
3. UV reading tube 139464N 18° – + 121°C
Replacing a Honeywell C 7027 A 1023/U UV flame detector is a good solution to make your equipment work again. We offer a wide range of Honeywell spare parts for burners, gas trains etc. We supply original Elster (Kromschröder) & Honeywell (Maxon) products.
If you have any queries about Honeywell industrial flame detectors or any other Honeywell spare parts, please write us at 624burner@gmail.com, quoting the item code C7027A1023/U.
- Commodity code 85402080
- Country of origin US
- EAN code 085267038744