}, 1000) } });
0 Cart
Kromschroeder catalog
Honeywell catalog

Honeywell C7027A1031/U UV flame detector

Brand: Honeywell
SKU: C7027A1031/U
Quantity:
+
PRICE ON REQUEST
624burner@gmail.com
Shipping methods

TNT delivery service

Pick up in our office

Payment methods

Invoice payment

Cash

Honeywell C7027A1031 flame sensors are used to detect the presence of ultraviolet radiation emitted by a flame. They work in conjunction with Honeywell flame control systems to detect flames in gas, oil and combined burners.

Characteristics and Features:

- The C7027A1031/U flame detectors are compatible with the R7249A, R7290A, R7749B and R7849A amplifiers, as well as with the corresponding Honeywell control devices.

- The Resideo C7027A1031/B flame sensor has a built-in cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.

- Due to its compact size, the C7027A1031 sensors are well suited for installation on purge pipes.

- With proper installation, the C7027A1031 sensors can operate at a pressure of up to 5 psi.

- In cases of difficult flame reading, two C7027A1023 detectors can be connected in parallel.

- The C7027A1031/U photocell is used exclusively with the R7851B flame amplifier and corresponding Honeywell control devices.

- Flame detectors C7027A1031/U have a built-in cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.

Additional features include:

- Operating temperature range from -18°C to 102°C or -40°C to +102°C, depending on the model.

- Maximum pressure: 5 psi (34.5 kPa).

- Installation: Cuff with 1/2-14 NPSM internal thread for installation on a ½-inch inspection tube.

- Electrical connections: Two wires 6 feet long [1.83 m], color-coded, NEC Class 1. (One model comes with wires 24 feet long [7.32 m]). The back of the detector has a clamping contact for a ½-inch flexible metal conductor. (There are also models with a pressure contact and an internal thread of ½ inch).

- Spare parts: Flange seal 129685.

- Operating temperature range: -18°C to +121°C or -40°C to +121°C, depending on the model.

- Maximum allowable pressure: 5 psi (34.5 kPa).

- Installation: Cuff with 1-11-1/2 NPSM internal thread for installation on a one-inch inspection tube. (The model with DIN C7035A1064 certificate has a thread 1-11 BSP.P1).

Spare parts include:

1. Flange seal 129808.

2. Tube for reading ultraviolet radiation 139464M with a temperature range from -18°C to +121°C.

3. 139464N UV reading tube with temperature range from -18°C to +121°C.



Replacing a Honeywell C 7027 A 1031/U UV flame detector is a good solution to make your equipment work again. We offer a wide range of Honeywell spare parts for burners, gas trains etc. We supply original Elster (Kromschröder) & Honeywell (Maxon) products.

If you have any queries about Honeywell industrial flame detectors or any other Honeywell spare parts, please write us at 624burner@gmail.com, quoting the item code C7027A1031/U.

  • Commodity code 85402080
  • Country of origin US
  • EAN code 4046911026148